Flame Arrester NK-FA22T

GNITION OF GAS/AIR VAPOR-CLOUDS EXTERNAL ATMOSPHERIC EXPLOSION
During filling of a storage tank and depending upon weather conditions explosive gas/air vapor clouds can develop in case they ignite due to external to protect the tank gets in touch with both flame and explosion shock wave. The provided device has to prevent a flashback and long burning poof.

MODEL NAME : NK-FA22T

NK-FA22T PHOTO

BURNING TEST

SPECIFICATIONS

MODEL NAME NK-FA22T
TYPE END-LINE FLAME ARRESTER
SIZE 2” THROUGH 12”
INSTALLATION VERTICAL
CLASSIFICATION DEFLAGRATION FLAME ARRESTER
NORMAL WORKING PRESSURE BELOW 10000mmH2O (STANDARD SPECIAFICATION)
EXPLOSION GAS GROUP IIA(standard), IIB/IIC(for special application)

MATERIALS

PART NAME MATERIALS STANDARD MATERIALS OPTIONAL
BODY C.S / SUS304 / SUS316 / ALUMINUM Hastelloy, Alloy 20, Monel, Inconel
ELEMENT 316L SS Hastelloy, Alloy 20, Monel, Inconel
HOUSING C.S / SUS304 / SUS316 / ALUMINUM Hastelloy, Alloy 20, Monel, Inconel
HOOD 304 SS / 316SS 316L SS
BOLT and NUT C.S / 304 SS / 316 SS 316L SS

DESIGN AND FUNCTION
Model NK-FA22T type is mounted on the end of a vent pipe from the tank. Vapors are allowed to escape into the atmosphere and air can be drawn into the tank through the flame element. The flame arrester consists of a spiral wound and crimped bank element.
The flame arrester is installed where it is not necessary to conserve vapor losses but low flash point solvent liquid must be protected against fire and explosion from exterior ignition sources.

INSPECTION AND INSTALLATION
All NEOTECHKOREA flame arresters are bi-directional and the installation on a tank or piping system depends to a great extent on the design of the system. The Model NK-FA22T is recommended for vertical installation on roof of tank or venting to atmosphere.

DRAWING AND DIMENSION

SIZE I.D L H
2” 50 240 280
3” 80 350 280
4” 100 395 295
6” 150 476 340
8” 200 584 360
10” 250 675 440
12” 300 759 440

UNIT : mm